CCTV Flame Detector - 20/20CTIN (NTSC) & CTIP (PAL)

The SharpEye CCTV Flame Detector (20/20CTIN and 20/20CTIP) is a self-contained, triple-spectrum, optical flame detector that incorporates a video color camera. The detector's IR sensors and spectral band pass filters have been selected to ensure the greatest degree of spectral matching to the radiant energy emissions of fire and the lowest degree of matching to non-fire stimuli.

The color video camera enables the user to investigate the monitored area, to identify the fire's source and location, and help select the best response to the situation (activation of fire suppression means).
Configuration can be made to issue a live color video picture signal at all times, on request or only when a fire is detected. Therefore, the detector is also useful for standard CCTV purposes.

The patented triple IR circuit is designed to respond only to flickering radiation signal (1 to 10 Hz) in the spectral bands ranging from 4.0 to 5.0 microns. The SharpEye CCTV Flame Detector is extremely sensitive. It can detect a 1ft.2 (0.1m2) gasoline pan fire at 100 ft. (30m) in less than 10 seconds. The sensitivity is user-programmable, offering 4 ranges of detection.

The video signal output of the CCTV Flame Detector can be either NTSC or PAL.

Main Features:

  • Live Color Video Image
  • Triple Spectrum Design
  • Sensitivity Selection
  • User Programmable Configuration
  • Highly Immune to False Alarms
  • Automatic and Manual Built-In Test (BIT)
  • Standard 4-wire Connection
  • 4-20mA sink or source (3-4 wires) configuration
  • RS-485 Modbus Compatible
  • MTBF Minimum 43,000 Hours
  • 3-Year Warranty
  • UL, ATEX, GOST R & Gost K Approved

Applications:

  • Aircraft Hangars - landing gear pits, under-wing and over-wing protection
  • Automotive - manufacturing, paint spray booths
  • Chemical Industry - production, storage, transportation
  • Explosives & Munitions - handling and storage
  • Oil & Gas - exploration, production, storage and offloading
  • Offshore Platforms - fixed rigs and floating vessels FPSO
  • Onshore - refineries, loading terminals, pipelines
  • Paint - manufacturing facilities
  • Petrochemicals - production, storage, shipping facilities
  • Pharmaceutical Industry
  • Power Generation Facilities - pump areas, generator rooms, unmanned stations, gas-fired and coal-fired reactors
  • Printing Industry - solvent handling, presses, drying processes
  • Tank Farms - floating-roof and fixed-roof tank areas
  • Warehouses - storage facilities for flammable materials
  • Waste Disposal Facilities - incineration, processing and storage of flammable waste materials (solids, liquids, gases)

General Specifications

Spectral Response Three IR Bands
CCTV Picture Enables the user to identify a 1 ft2 (0.1m2) gasoline flame from 100 ft. (30m) offering a "live video" image of the monitored area.
Detection Range
(Highest Sensitivity Setting 
for 1 sq.ft. pan fire)

 

Gasoline fire at 200 ft (60m)  JP4 fire at 150 ft (45m)
N-Heptane fire at 200 ft (60m) Kerosene fire at 150 ft (45m)
Alcohol 95% fire at 150 ft (45m) Methane* fire at 60 ft (18m)
Diesel Fuel fire at 140 ft (42m) Propane* fire at 60 ft (18m)
* 0.5m plume fire
Response Time Typical 5 sec.
Adjustable Time Delay Up to 30 seconds
Sensitivity Range 4 Sensitive Ranges for 1 ft2 (0.1m2) gasoline pan fire from 50 ft (15m) to 200 ft (60m)
Field of View IR3: 90° horizontal, 90° vertical
CCTV: 90° horizontal, 65° vertical
Built-in-Test Manual and automatic BIT
Temperature Range
Operating:  -15°F (-10°C) to 131°F (55°C)
Operating without Video: -40°F (-40°C) to 160°F (70°C)
Storage: -22°F (-30°C) to 140°F (60°C)
Humidity Up to 95%

Electrical Specifications

Power Supply Operating Voltage: 18-32 VDC
Power Consumption Max. 150mA in stand-by
Max. 200mA in alarm
Electrical Connection 2 x 3/4" - 14NPT conduits
or 2 x M25 x 1.5 mm ISO
Electrical Input Protection

According to MIL-STD-1275A

Electromagnetic Compatibility EMI/RFI protected (comply to CE requirements)

Outputs:

Relays
Alarm 2A at 30 VDC, 0.5A at 250 VAC
Fault  5A at 30 VDC and 250 VAC
Fault relay normally closed, others normally open
4-20mA  Sink (source option) configuration
Fault:   0 +0.5mA
BIT Fault: 2mA ±10%
Normal:  5mA ±10%
Warning:  10mA ±5%
Alarm:   15mA ±5%
Resistance Loop:  100-600 Ohm
RS-485  The RS-485 communication link can be used in installations with computerized controllers. The RS-485 is Modbus compatible
Color Video Image Accessible via a standard NTSC or PAL video output connection that can be connected to standard video equipment for viewing, recording and scanning video images.

Mechanical Specifications

Dimensions 4.7" x 5.2" x 5.2" (120 x 132 x 132 mm)
Weight
Aluminum 8.1Lb (3.7 Kg)             
St.St 316L 14.3Lb (6.5 Kg) 
Enclosure Aluminum, heavy-duty copper free (less than 1%), white epoxy enamel finish.
Optional - Stainless Steel 316L with electro polish finish
Environmental Standards Meets MIL-STD-810C for Humidity, Salt & Fog, Vibration, Mechanical
Shock, High Temp, Low Temp
Water and Dust IP66 and IP67 per En60529
NEMA 250 6P

Hazardous Area Approvals

ATEX EX II 2G, EExd IIB + H2 T5 (55°C)
EX II 2G, EExde IIB + H2 T5 (55°C)
UL  Class I, Groups C & D
GOST R 1ExdIIBT5/H2

Accessories

Fire Simulator  20/20-310
Swivel Mount 20/20-003 (St. St. 316L)

Specifications subject to changes

  Download Datasheet PDF
  Download Manual PDF 

 

More Information Click here for more information